Pump Wire Size Chart
The pump and alarm should always be on separate fuses or breakers. Use the following chart to determine the proper size of wire to use to power the pump.
Maximum Copper Cable Length
For Various Motors & Wire Gauges. Lengths are in feet.
| Motor Rating | Copper Wire Size | ||||||
|---|---|---|---|---|---|---|---|
| Volts | HP | 14 | 12 | 10 | 8 | 6 | 4 |
| 115 | 1/3 | 130 | 210 | 340 | 540 | 840 | 1300 |
| 115 | 1/2 | 100 | 160 | 250 | 390 | 620 | 960 |
| 115 | 6/10 | 100 | 160 | 250 | 390 | 620 | 960 |
| 230 | 1/3 | 550 | 880 | 1390 | 2190 | 3400 | 5250 |
| 230 | 1/2 | 400 | 650 | 1020 | 1610 | 2510 | 3880 |
| 230 | 6/10 | 290 | 460 | 740 | 1170 | 1820 | 2810 |
| 230 | 3/4 | 300 | 480 | 760 | 1200 | 1870 | 2890 |
| 230 | 1 | 250 | 400 | 630 | 990 | 1540 | 2380 |
| 230 | 1 1/2 | 190 | 310 | 480 | 770 | 1200 | 1870 |
| 230 | 2 | 150 | 250 | 390 | 620 | 970 | 1530 |
How to use the chart
- Measure the length of wire needed to reach from the fuse or breaker box to the pump
- Determine the horsepower rating for the pump.
- Determine whether the pump will be installed to run using a 115V or 230V circuit. (higher horsepower pumps and/or long runs require a 230V circuit)
- Select the row on the chart which corresponds to the horsepower and voltage ratings for the pump.
- Working from the left, select the first cell whose number is higher than the needed length of wire.
- The required wire size is at the top of the chosen column.