Pump Wire Size Chart

The pump and alarm should always be on separate fuses or breakers. Use the following chart to determine the proper size of wire to use to power the pump.

Maximum Copper Cable Length

For Various Motors & Wire Gauges. Lengths are in feet.

Motor RatingCopper Wire Size
VoltsHP141210864
1151/31302103405408401300
1151/2100160250390620960
1156/10100160250390620960
2301/35508801390219034005250
2301/24006501020161025103880
2306/10290460740117018202810
2303/4300480760120018702890
230125040063099015402380
2301 1/219031048077012001870
23021502503906209701530

How to use the chart

  1. Measure the length of wire needed to reach from the fuse or breaker box to the pump
  2. Determine the horsepower rating for the pump.
  3. Determine whether the pump will be installed to run using a 115V or 230V circuit. (higher horsepower pumps and/or long runs require a 230V circuit)
  4. Select the row on the chart which corresponds to the horsepower and voltage ratings for the pump.
  5. Working from the left, select the first cell whose number is higher than the needed length of wire.
  6. The required wire size is at the top of the chosen column.